ESB 1075 CLIENT – M/S Pranav Eximp Pvt. Ltd., Test Report Durga Viralimalai – 621 316 Pudukottai Dt.. Page No: 1 Switchgears Make : AE Serial No. 10 / 7 / 004088 / 45 CALIBRATION TEST FOR AMMETER Date: 02nd December 2009 RATIO : 30 / 5 Amps Reading Reading in the Current Calculated in the Ammeter to...
ESB 1075 Durga Switchgears CLIENT – M/S Pranav Eximp Pvt. Ltd., Viralimalai – 621 316 Pudukottai Dt.. Test Report Page No: 1 Make : AE Serial No. 10 / 7 / 004088 / 45 CALIBRATION TEST FOR AMMETER Date: 02nd December 2009 RATIO : 30 / 5 Amps TEST RESULTS ARE FOUND SATISFACTORY. Current Injected in %age Calculated secondary current in Amps Reading in the Standard Meter Reading in the Ammeter to be Calibrated 20% 1.0 6.0 6.1 40% 2.0 12.0 12.0 60% 3-0 18.0 18.2 80% 4.0 24.0 23.9 100% 5.0 30.0 30.1...