RM6 - Medium Voltage Distribution Civil engineering and installation manual 07897071EN01 Rev.11 04/2017
RM6 - Civil engineering and installation manual
Table of Contents
Foreword ......................................................................................... 6 Foreword................................................................................................................. 6 Safety Instructions .................................................................................................. 7 Disposal of the Equipment at End-of-Life ............................................................... 7
Generale Description ....................................................................... 8 Circuit-breaker and Switch Function ....................................................................... 8 Fuse- Switch and Switch Function.......................................................................... 8 ”Switchboard Coupling” switch and Circuit-breakers .............................................. 8 Cable Connection Function .................................................................................... 9 Metering Cubicle ..................................................................................................... 9 Single-line Diagrams............................................................................................. 10 Range Sizes and Weights .................................................................................... 11 Transport .............................................................................................................. 16 Handling................................................................................................................ 17 Unpacking on Site................................................................................................. 19 Storage ................................................................................................................. 21 Charactéristics ...................................................................................................... 22 Identification.......................................................................................................... 23 Before Installation and Energising ........................................................................ 24 Unit with Manometer ............................................................................................. 24 Unit with Pressure Switch ..................................................................................... 25
Installation Recommendation ........................................................ 27 Reminder .............................................................................................................. 27 Temperature ......................................................................................................... 27 Example of Correct Installation ............................................................................. 28
Sizing of the Civil Engineering ....................................................... 29 For Network Switch or Network Circuit-breaker.................................................... 29 For Fuse-Switches ................................................................................................ 30 For DE- Mt Metering Cubicle ................................................................................ 32 Duct Detail for Switchboard with MV Metering ..................................................... 33
Fitting and Fixing on the Civil Engineering .................................... 34 Dimensions of RM6 RE with an Extension Module ............................................. 34 Preparing the Ground Fixing ............................................................................... 35 Fixing to the Ground ............................................................................................. 36 Installing the Substation for Resistance to Internal Arc ....................................... 37
Connection Instructions ................................................................. 40 Foreword............................................................................................................... 40 Type of Usable Connections................................................................................. 41 Connecting the HV Cables ................................................................................... 42 Instructions ........................................................................................................... 43 Methods and Fabrication of Cable Connections for Single Pole Cables .............. 44 LV Compartment Customer Power supply for DE-Mt Cubicle .............................. 52 Current Transformer (CT) Intensities and Temperatures for DE-Mt Cubicle ........ 53 Switch, Circuit-breaker, Earthing Switch Indication .............................................. 54 Fuse Blowing Indication (optional supply) ............................................................ 54 Fault Tripping Indication (optional supply) ............................................................ 54 Tripping Coil (optional supply) .............................................................................. 55
07897071EN01-11
3
RM6 - Civil engineering and installation manual
Table of Contents (suite)
Pressure Switch Connection................................................................................. 56 Connecting a Sepam 10 Relay ............................................................................. 57 VIP400 / VIP410 Connection ................................................................................ 71 Installing an ATS (Automatic Transfer System) .................................................... 75 BTA Function ........................................................................................................ 76 Installing an ATS/ACO .......................................................................................... 76 Fitting the T200I Support Kit ................................................................................. 77 Installing the T200I and Connecting it to the RM6 ................................................ 77 Detection Sequence (ATS/VD23) ......................................................................... 79
4
07897071EN01-11
RM6 - Civil engineering and installation manual
07897071EN01-11
Notes
5
Foreword
RM6 - Civil engineering and installation manual
Foreword Foreword Important Informations Notice Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call CAUTION to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
INFORMATION-ADVICE We draw your attention on this particular point.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
6
07897071EN01-11
RM6 - Civil engineering and installation manual
Foreword
CAUTION The total or partial reproduction of this manual is prohibited and only the Schneider Electric agents have an exclusive right to use.
Safety Instructions Safety Rules
SOLVENTS AND ALCOHOL FORBIDDEN
HIGH-PRESSURE CLEANER FORBIDDEN
Disposal of the Equipment at End-of-Life WARNING This equipment contains SF6 gas. SF6 is a powerful greenhouse gas and is harmful for the environment. Prior to disposal of the equipment at end-of-life, the SF6 gas must be recovered in order for it to be recycled, reclaimed or destroyed. ● DO NOT carry out any dismantling operations unless authorized. ● DO NOT handle SF6 gas unless certified. ● DO NOT release SF6 gas to the atmosphere. Penalties may apply according to local regulations and rules (Regulation (EU) N°517/2014 for all European countries). Schneider Electric offers a complete service to dismantle and recycle Medium Voltage equipment and SF6 gas at end-of-life. This service is compliant with IEC 62271-4 and conforms to local regulations. Please contact Schneider Electric for details.
07897071EN01-11
7
General Description
RM6 - Civil engineering and installation manual
General Description Circuit-breaker and Switch Function A : operating mechanism front plate comprising the
G
mimic diagram
C
D K L
N F E P
B : information plates C : earthing switch operating shaft D : switch operating shaft E : function position indicator F : voltage indicator
B A
G : LV connection access trunking H : connection bushing access panel
M
K : VIP40/45 - VIP400/410 protection relays
H
L : D function opening pushbutton M : rating plate N : pressure switch or gauge label P : pressure switch or gauge
IDI
Fuse- Switch and Switch Function A : operating mechanism front plate comprising the
G
C
D
N F E P
mimic diagram B : information plate C : earthing switch operating shaft D : switch operating shaft
B
E : function position indicator
A
F : voltage indicator G : LV connection access trunking H : connection bushing access panel J : rating plate N : pressure switch or gauge label
J H
P : pressure switch or gauge
IQI
”Switchboard Coupling” switch and Circuit-breakers 1 : DE- BC station with earthing switch
D
A : control panel featuring the mimic panel
B
B: earthing switch operating shaft C: switch operating shaft D: voltage indicator
F A
C
E: connection bushing access panel F: rating plate
8
E
07897071EN01-11
RM6 - Civil engineering and installation manual
General Description
2 : DE- IC station with earthing switch
D A: control panel featuring the mimic panel B: earthing switch operating shaft
B
G
C: switch operating shaft D: voltage indicator
C
A
E: connection bushing access panel F: plate characteristics
F E
G: characteristics plates
Cable Connection Function Example presented : DE- O A: characteristics plate
A
B: rating plate C: connection bushing access panel
B
C
Metering Cubicle 1: LV compartment 2: voltage transformer access panel 3: characteristics plate 4: access panel to current transformer 5: LV compartment
3
2
4
without LV compartment
07897071EN01-11
1
5
with LV compartment
9
General Description
RM6 - Civil engineering and installation manual
Example of Single-line Diagrams NE = No Extensible DE = Double Extensible LE = Left Extensible RE = Right Extensible
NE - D
RE - DIDI
DE - IIBI
Transformer protection by ’circuit-breaker’
Transformer protection by ’circuit-breaker’
Line protection by ’circuit-breaker’
DE - III
NE - IQI
NE - IDI
Network ’switch ’
Transformer protection by ’fuse- switch combinaison’
Transformer protection by’ circuit-breaker’
10
DE - DD
DE - IDD
Transformer protection by ’circuit-breaker ’
Transformer protection by ’circuit-breaker’
DE - IIBc
Switchboard coupling ’circuit-breaker’
07897071EN01-11
RM6 - Civil engineering and installation manual
General Description
Range Sizes and Weights 1 Function Range function NE I D B DE I D B Q cable connexion RE O LE DE bus coupler DE Ic Bc
weight (kg) 135
length (mm) L= 572
135
L’=472+30+30=532 L’=572+30+30=632
185
L’=472+30+30=532
135
L’=472+30=502
1142 30
30
L’=472+30+30=532 145
L’=572+30+30=632
L
710
L’
30
30
30 30
NE
RE
LE
DE
L
L L’
L L’
L L’
NE = No Extensible DE = Double Extensible LE = Left Extensible RE = Right Extensible
2 Functions Range Basic function
weight (kg)
length (mm)
NE
180
L= 829
RE
QI DI, BI II II
155 L’= 829+30= 859
1142
L L’
07897071EN01-11
11
General Description
RM6 - Civil engineering and installation manual
2 Functions Range / Free Combination function NE
length (mm) L= 1052
LE
L’=1052+30=1082
RE DE
L’=1052+30+30=1112
L L’ All function can be FREE combination Below possible example : function II ID IQ DD DQ QQ
IO DI QI BB
OI IB OQ
OO BI QO
QD
BQ
QB
weight (kg) 205 215 240 225 250 275
3 Functions Range Basic function NE IQI
RE
DE
weight (kg) length (mm) 275 L= 1186
III IDI
240
IBI RE- IQI
250 275
RE- III RE- IDI
240
RE- IBI IQI
250 275
III IDI
240
IBI
250
L’ = 1186+30=1216
L’ = 1186+30+30=1246
L L’
12
07897071EN01-11
RM6 - Civil engineering and installation manual
General Description
3 Functions Range / Free Combination function NE
length (mm) L= 1532
LE RE
L’=1532+30=15622
DE
L’= 1532+30+30=1592
L L’ All function can be FREE combination Below possible example : function III IIO IOO IID IIB IIQ IDD IBB IQD QDI IQQ DDD QQQ
weight (kg) OOO IOI OIO IDI IBI IQI DID BIB IDQ QID QIQ BBB
OII OOI DII BII QII DDI BBI DIQ DQI
305 305 305 315 315 340 325 325 350 350 375 335 410
With Bus Coupler function NE DE
length (mm) L= 1532 L’= 1532+30+30=1592
L L’ Below possible example :
07897071EN01-11
function
weight (kg)
IIIc IIBc DIIc IQIc IQBc DDIc DDBc QQIc QQBc
320 330 330 355 365 340 350 390 400
IDIc BIIc QIIc QIBc BBIc BBBc
IBIc
13
General Description
RM6 - Civil engineering and installation manual
4 Functions Range Basic function NE IIQI IIII IIDI / IIBI QIQI BIBI / DIDI DIDI RE IIQI IIII IIDI / IIBI QIQI BIBI DIDI DE IIQI IIII IIDI / IIBI
weight (kg) 355 320 330 390 340 340 355 320 330 390 340 340 355 320 330
length (mm) L = 1619
L’ = 1619+30 = 1649
L’ = 1619+30+30 = 1679
L L’ NE = No Extensible DE = Double Extensible LE = Left Extensible RE = Right Extensible
5 Functions Range function NE IIIQI IBIQI IIIII IIIDI / IIIBI IQIQI IBIBI / IDIDI RE / IIIQI LE IBIQI
DE
weight (kg) 485 495 450 460 520 470
length (mm) L = 2000
490
L’ = 2000+30 = 2030
IIIII
500 455
IIIDI/ IIIBI IQIQI
465 525
IBIBI/ IDIDI IIIQI
475
IBIQI
505
IIIII IIIDI/ IIIBI
460 470
IQIQI IBIBI/ IDIDI
530 480
495
L L’
L ’= 2000+30+30 = 2060
Option Arrester option Dimensions en mm 175
1142
710 859
14
07897071EN01-11
RM6 - Civil engineering and installation manual
General Description
Metering Cubicle With LV compartment function DE_Mt
weight (kg) 420
length (mm) L= 1106
1606
L
901
Without LV compartment function DE_Mt
weight (kg) 400
length (mm) L= 1106
1174
L
07897071EN01-11
901
15
General Description
RM6 - Civil engineering and installation manual
Transport Centre of Gravity Do not handle the cell from the face
CAUTION
plate. 1 : high centre of gravity Handle the cell carefully so as not to cause deformation or damage.
1
Wedge the RM6 unit securely during transport.
DO NOT STACK
CAUTION Do not place anything on the RM6 unit. Do not walk on the RM6 unit.
b Make sure the delivered RM6 unit is complete. b Carry out a visual inspection of the functional components. b Verify the characteristics indicated on the nameplates, compared to the initial order. Refer to the “Characteristics” chapter. b The plastic cover must be in position on the RM6 unit and in good condition when it arrives.
16
07897071EN01-11
RM6 - Civil engineering and installation manual
General Description
Handling A handling pallet is fixed beneath the RM6 switchgear. This device enables fork handling of the devices.
Silk- screen Printed Instructions on the Transport Cover
CAUTION It is important to pay particular attention to the information affixed to the transport cover before carrying out any kind of handling operations.
Protéger de la pluie
Manipuler avec soin
Soulever dans ce sens
Protéger du soleil
maxi 70°C
Température de stockage Centre de gravité haut
Ne pas marcher dessus
Ne pas empiler
mini --- 40°C
Handling by Forklift Truck
1
2
RM6
The handling solution 1 is to be used only for narrow areas where handling solution 2 is impossible.
07897071EN01-11
17
General Description
RM6 - Civil engineering and installation manual
Handling by Slings with Hooks If the minimum sling lengths cannot be implemented, use a lifting beam.
A: nut and screws HM12 B: WLL (Working Load Limit) = 400 kg ...