Appendix A Data for the IEEE 24 bus Reliability Test System The IEEE 24 bus Reliability Test System (or IEEE 24 bus RTS) [193], as shown in Fig.A.1, is used in the thesis for different simulations conducted in Chapter 4, Chapter 5, Chapter 6 and Chapter 7. The bus data and transmission line data are...


Description

Data for the IEEE 24 bus Reliability Test System

The IEEE 24 bus Reliability Test System (or IEEE 24 bus RTS) [193], as shown in Fig.A.1, is used in the thesis for different simulations conducted in Chapter 4, Chapter 5, Chapter 6 and Chapter 7. The bus data and transmission line data are given at 100 MVA in Table A.1 and Table A.2 respectively. The market data for reactive power offers (Bids) [57], as used in Chapter 5 and Chapter 7, is given in Table A.3.

Fig.A.1: Single line diagram of the IEEE 24 bus Reliability Test System

Appendix A: Data for the IEEE 24 bus Reliability Test System

2013

Table A.1: Bus data for the IEEE 24 bus Reliability Test System (in p.u.) Bus No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

PG,i 1.3796 1.3796 0.0000 0.0000 0.0000 0.0000 2.7231 0.0000 0.0000 0.0000 0.0000 0.0000 4.6406 0.0000 1.4069 1.4069 0.0000 3.6307 0.0000 0.0000 3.6307 2.7228 5.9907 0.0000

PD,i 1.0800 0.9700 1.8000 0.7400 0.7100 1.3600 1.2500 1.7100 1.7500 1.9500 0.0000 0.0000 2.6500 1.9400 3.1700 1.0000 0.0000 3.3300 1.8100 1.2800 0.0000 0.0000 0.0000 0.0000

QD,i 0.2200 0.2000 0.3700 0.1500 0.1400 0.2800 0.2500 0.3500 0.3600 0.4000 0.0000 0.0000 0.5400 0.3900 0.6400 0.2000 0.0000 0.6800 0.3700 0.2600 0.0000 0.0000 0.0000 0.0000

Vi 1.0350 1.0350 0.9913 0.9982 1.0186 1.0126 1.0250 0.9923 1.0022 1.0283 0.9892 1.0017 1.0200 0.9800 1.0140 1.0170 1.0392 1.0500 1.0231 1.0382 1.0500 1.0500 1.0500 0.9818

Vimax 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05

Vimin 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95

Base KV 138 138 138 138 138 138 138 138 138 138 230 230 230 230 230 230 230 230 230 230 230 230 230 230

Table A.2: Transmission line data for the IEEE 24 bus Reliability Test System (in p.u.)

Line No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

From Bus No. 1 1 1 2 2 3 3 4 5 6 7 8 8 9 9 10 10 11 11 12 12 13 14

To Bus No. 2 3 5 4 6 9 24 9 10 10 8 9 10 11 12 11 12 13 14 13 23 23 16

R

X

Bch (Full)

0.0026 0.0546 0.0218 0.0328 0.0497 0.0308 0.0023 0.0268 0.0228 0.0139 0.0159 0.0427 0.0427 0.0023 0.0023 0.0023 0.0023 0.0061 0.0054 0.0061 0.0124 0.0111 0.0050

0.0139 0.2112 0.0845 0.1267 0.1920 0.1190 0.0839 0.1037 0.0883 0.0605 0.0614 0.1651 0.1651 0.0839 0.0839 0.0839 0.0839 0.0476 0.0418 0.0476 0.0966 0.0865 0.0389

0.4611 0.0572 0.0229 0.0343 0.0520 0.0322 0.0000 0.0281 0.0239 2.4590 0.0166 0.0447 0.0447 0.0000 0.0000 0.0000 0.0000 0.0999 0.0879 0.0999 0.2030 0.1818 0.0818

Max. Line Rating 1.7500 1.7500 1.7500 1.7500 1.7500 1.7500 4.0000 1.7500 1.7500 1.7500 1.7500 1.7500 1.7500 4.0000 4.0000 4.0000 4.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 Table A.2 Contd…

Dept. Of Electrical Engg., Faculty of Engineering, Dayalbagh Educational Institute, Agra-282110

300

Appendix A: Data for the IEEE 24 bus Reliability Test System

2013

Table A.2 Contd… 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38

15 15 15 15 16 16 17 17 18 18 19 19 20 20 21

16 21 21 24 17 19 18 22 21 21 20 20 23 23 22

0.0022 0.0063 0.0063 0.0067 0.0033 0.0030 0.0018 0.0135 0.0033 0.0033 0.0051 0.0051 0.0028 0.0028 0.0087

0.0173 0.0490 0.0490 0.0519 0.0259 0.0231 0.0144 0.1053 0.0259 0.0259 0.0396 0.0396 0.0216 0.0216 0.0678

0.0364 0.1030 0.1030 0.1091 0.0545 0.0485 0.0303 0.2212 0.0545 0.0545 0.0833 0.0833 0.0455 0.0455 0.1424

5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000

Table A.3: Market data of reactive power offers (Bids) for the IEEE 24 bus Reliability Test System Bus No.

Unit a0 No. ($) 1 0.96 2 0.94 1 3 0.85 4 0.83 1 0.50 2 0.42 2 3 0.69 4 0.65 1 0.75 7 2 0.80 3 0.70 1 0.68 13 2 0.70 3 0.75 1 0.94 14a 1 0.65 2 0.50 3 0.60 15 4 0.55 5 0.52 6 0.51 16 1 0.50 18 1 0.90 21 1 0.80 1 0.42 2 0.50 3 0.45 22 4 0.48 5 0.49 6 0.55 1 0.90 23 2 0.95 3 0.86 a Synchronous condenser (SC)

m1 ($/MVAr-h) 0.86 0.82 0.79 0.82 0.54 0.42 0.68 0.62 0.61 0.75 0.65 0.50 0.54 0.60 0.81 0.60 0.58 0.73 0.61 0.50 0.51 0.50 0.85 0.75 0.42 0.48 0.42 0.44 0.45 0.46 0.85 0.89 0.80

m2 ($/MVAr-h) 0.86 0.82 0.79 0.82 0.54 0.42 0.68 0.62 0.61 0.75 0.65 0.50 0.54 0.60 0.81 0.60 0.58 0.73 0.61 0.50 0.51 0.50 0.85 0.75 0.42 0.48 0.42 0.44 0.45 0.46 0.85 0.89 0.80

m3 ($/MVAr-h2) 0.46 0.45 0.39 0.40 0.28 0.35 0.39 0.37 0.43 0.36 0.32 0.31 0.39 0.50 0.00 0.30 0.25 0.38 0.27 0.26 0.27 0.30 0.48 0.41 0.17 0.20 0.38 0.35 0.33 0.32 0.48 0.55 0.45

QGmax (MVAR) 10 10 30 30 10 10 30 30 60 60 60 80 80 80 200 6 6 6 6 6 80 80 200 200 16 16 16 16 16 16 80 80 150

Dept. Of Electrical Engg., Faculty of Engineering, Dayalbagh Educational Institute, Agra-282110

QGmin (MVAR) 0 0 -25 -25 0 0 -25 -25 0 0 0 0 0 0 -50 0 0 0 0 0 -50 -50 -50 -50 -10 -10 -10 -10 -10 -10 -50 -50 -25