Title | Electrical Engineering-Electrical Plan (Lighting and Power Layout) Example |
---|---|
Course | Bachelor of Science in Electrical Engineering |
Institution | Polytechnic University of the Philippines |
Pages | 5 |
File Size | 403.2 KB |
File Type | |
Total Downloads | 64 |
Total Views | 140 |
This document also contained a Riser Diagram and a Site Location Plan of the house used as an example.
Nice and organized example. Hand drawn but scanned so it is clear and everyone will be able to understand....
Lighting and Power Layout Examples with Riser Diagram and Site Location Plan
LOAD SCHEDULE AND COMPUTATION CKT No.
LOAD DESCRIPTION
VA RATING
VOLT
AMPERE
CB RATING
CONDUCTOR SIZE
CONDUIT SIZE
1
8 - LO @ 60W
480
230
2.09
15AT
2-2.10 mm2 CU Type THWN + 1-2.0 Cu Conductor Type TW for Neutral
16 mm diameter PVC
2
6 - CO @ 200W
1200
230
5.22
20AT
2-2.10 mm2 CU Type THWN + 1-2.0 Cu Conductor Type TW for Neutral
16 mm diameter PVC
3
1 - Microwave Oven @ 1700W
1700
230
7.39
20AT
2-2.10 mm2 CU Type THWN + 1-2.0 Cu Conductor Type TW for Neutral
16 mm diameter PVC
4
1 - Rice Cooker @ 800W
800
230
3.48
20AT
2-2.10 mm2 CU Type THWN + 1-2.0 Cu Conductor Type TW for Neutral
16 mm diameter PVC
5
1 - Washing Machine @ 500W
500
230
2.17
20AT
2-2.10 mm2 CU Type THWN + 1-2.0 Cu Conductor Type TW for Neutral
16 mm diameter PVC
20.35
Use:
1 - 30AT amp. MBC 2 pole, 230V 2 - 5.5 mm2 Cu Conductor Type THWN 1 - 2.0 mm2 Cu Conductor Type TW for Neutral
GENERAL NOTES
1. ALL ELECTRICAL INSTALLATION HEREIN ARE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE RULES, REGULATIONS AND REQUIREMENTS OF THE LOCAL ENFORCING AUTHORITY, 2. THE TYPE OF POWER SERVICE SUPPLIED IS 230 V, 1 Ǿ, 60 Hz 3. ALL CONDUCTORS ARE COPPER, MINIMUM SIZE SHALL BE 2.0mm2, UNLESS OTHERWISE SPECIFIED. 4. ALL MATERIALS ARE NEW AND OF THE APPROVED TYPE FOR THE LOCATION INTENDED. 5. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT AND LIGHTING FIXTURE ARE EFFECTIVELY GROUNDED. 6. MOUNTING HEIGHTS FOR SWITCHES IS 1.37M (ON THE CENTER OF THE BOX) AND 0.30M FOR CONVENIENCE OUTLETS, IUNLESS OTHERWISE SPECIFIED. 7. PULLBOXES ARE PROVIDED BY THE CONTRACTOR WHEN EVER NECESSARY, TO FACILITATE WIRE PULLING EVEN IF THESE ARE NOT INDICATED ON THE PLANS, PULLBOXES WERE SIZED IN ACCORDANCE WITH THE PEC. 8. NO BRANCH CIRCUIT CONDUCTOR SHALL HAVE A LOAD MORE THAN 80% OF ITS RATING. 9. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LISCENCED AND COMPETENT PROFESSIONAL OR REGISTERED ELECTRICAL ENGINEER, 10. TO PROVIDE EFFECTIVE GROUNDING SYSTEM FOR EQUIPMENT PROTECTION, USING MINIMUM 2,400mm x 20mm Ǿ GROUNDING ELECTRODE DIRECTLY BURIED....