Please calculate the question below in the space provided. Be sure to show all of your work!! 1) 35KVA, 600v Primary, 120/208v Secondary, 3 Phase 4 wire system.(12 Marks)
Assuming Dry−type Transformer :
a) What is the size of the Primary Fuse? (3 marks)
I primary =
KVA ×1000 Eline ×1.73
=
35 ×1000 =33.7 A 600 V ×1.73
MaximumCalculated Fuse Rating:
Rule 26 −254 ( 1)
PrimaryFuse Rating Max. =I primary × 1.25 ¿ 33.7 A ×1.25 ¿ 42.1 A Suggested Primary Fuse ¿ 42.1 A Stand ard Primary Fuse ¿ Table 13 ¿=40 A , ans .
b) What size Disconnect? (3 marks)
I primary =
KVA ×1000 Eline ×1.73
=
35 ×1000 =33.7 A 600 V ×1.73
Suggested Primary Fuse ¿ 33.7 A × 1.25=42.1 A
Use 40 A fused disconnects , ans .
C) What size T90 conductors for Line side AND Load Side?(3 marks)
Minimum Ampacity Rating : Rule26 −256 (1)(a) ¿ Ip×
1.25
¿ 33.7 A ×1.25 ¿ 42.1 A
Table 2 Conductor ¿ (¿ ):Three¿ 8 AWG T 90 Copper , ans .
D) What size T90 conductors from Transformer to Panel(Secondary feeder)? (3 marks)
I secondary=
35× 1000 =97.3 A 208× 1.73
Minimum Ampacity Rating=I s ×1.25=97.3 A × 1.25=121.6 A Conductor ¿Table 2 ¿ : Four ¿ 2 T 90 Copper , ans .
Please calculate the question below in the space provided. Be sure to show all of your work!! 2) 45KVA, 600v Primary, 120/208v Secondary, 3 Phase 4wire system(12 marks)
Assuming Dry−type Transformer :
a) What size T90 copper conductor from Transformer to Panel?(3 marks)
I s=
45 ×1000 =125.1 A 208× 1.73
Minimum Ampacity Rating=125.1 A × 1.25=156.4 A Table 2 Conductor ¿ (¿ ):Four ¿ 1∅ T 90 Copper , ans .
b) Size conduit from Disconnect to Transformer? (3 marks)
Ip=
45× 1000 =43.4 A 600× 1.73
Minimum Ampacity Rating=I p × 1.25=43.4 A × 1.25=54.25 A Table 2 Conductor ¿(¿):Three¿ 8 T 90Coppe r
Table 6 K '' Conduit ¿(¿):Use 3 / 4 ∨21mm conduit , ans .
C) Size conduit from Transformer to Panel?
¿a¿ Table 2 Conductor ¿(¿):Four 1∅ T 90 Copper Table 6 K Conduit ¿(¿):Use 2'' ∨53 mm conduit , ans .
D) Bonding conductor from Secondary Side? (3 marks)
¿a¿
Minimum Ampacity Rating=156.4 A Bonding Conductor (Table 16):¿ 6 AWG Copper , ans .
Please calculate the question below in the space provided. Be sure to show all of your work!!
3) 80 KVA, 600v Primary, 120/208v Secondary, 3 Phase 4 wire system.(24 marks)
Assuming Dry−type Transformer :
a) Primary fuse size? (3 marks)
I primary =
KVA ×1000 Eline ×1.73
=
80 ×1000 =77.1 A 600 V × 1.73
MaximumCalculated Fuse Rating:
Rule 26 −254 ( 1)
PrimaryFuse Rating Max. =I primary × 1.25 ¿ 77.1 A ×1.25 ¿ 96.4 A Suggested Primary Fuse S ize=96.4 A Standard Primary Fuse S ize=90 A , ans .
b) Size of disconnect? (3 marks)
I primary =
KVA ×1000 Eline ×1.73
=
80 ×1000 =77.1 A 600 V × 1.73
Suggested Primary Fuse ¿ 77.1 A × 1.25=96.4 A
Use 90 A Fused Disconnects , ans . c) Size of T90 Copper Conductor from:(6 marks) i) Main power to Disconnect(2 marks)
Ip=
80× 1000 =77.1 A 600× 1.73 Minimum Ampacity Rating=I p × 1.25=77.1 A × 1.25=96.4 A
Table 2 Conductor ¿(¿):Three¿ 3 AWG T 90 Copper ,ans .
ii) Load side of Disconnect (2 marks)
Minimum Ampacity Rating=I p × 1.25=77.1 A × 1.25=96.4 A Table 2 Conductor ¿(¿):Three¿ 3 AWG T 90 Copper ,ans .
iii) Transformer to Panel (2 marks)
I s=
80 ×1000 =222.3 A 208× 1.73 Minimum Ampacity Rating=I s ×1.25=222.3 A × 1.25=277.9 A
Table 2 Conductor ¿(¿):Four 250 kcmil T 90 Copper , ans .
d) Size of Panel? (3 marks)
I secondary=
KVA ×1000 Eline × 1.73
=
80 ×1000 =222.3 A 208 V ×1.73 Rule 26 −254 ( 1)
MaximumCalculated Fuse Rating:
Secondary Fuse Rating Max.=I s × 1.25
¿ 222.3 A × 1.25=277.9 A
Table 13 Standard Primary Fuse ¿ (¿)=250 A , ans . e) Size of conduit from disconnect to Transformer? (3 marks)
Minimum Ampacity Rating=I p × 1.25=77.1 A × 1.25=96.4 A Table 2 Conductor ¿(¿):Three ¿ 3 T 90 Copper Table 6 K Conduit ¿(¿):Use 35 mm conduit , ans .
f) Size of conduit from Transformer to Panel? (3 marks)
Minimum Ampacity Rating=I s ×1.25=222.3 A × 1.25=277.9 A Table 2 Conductor ¿ (¿ ):Four 250 kcmil T 90 Copper Table 6 K Conduit ¿(¿):Use 78 mm conduit , ans .
g) Secondary Bonding conductor? (3 marks)
Minimum Ampacity Rating=I s ×1.25=222.3 A × 1.25=277.9 A Bonding Conductor ( Table 16 ) :¿ 4 AWG Copper , ans ....