TECHNICAL SUBMITTAL FORM Project Name:

MSFT Dub 13

Project No.:

1179

Submittal No.:

TS-CSA-150

Revision No.:

1

To: Attention of: Date Issued: Response Req’d.:

RKD Kevin O’Sullivan 01-03-2021 15-03-2021

Product / Material / Equipment Details Product / Material / Equipment

Tate Structural Ceiling Grid

Provide full name and also names of any companion items to be used

Supplier / Manufacturer

Tate

Provide full name and address

Intended Use

Ceilings in mechanical gallery

Provide full details of the intended use of the Product / Material / Equipment

Is the Product / Material / Equipment as specified or is an alternative proposed? Are there any derogations / deviations from the Project Specifications for this item? Indicate the basis for equivalence of the alternative solution proposed.

As specified

No

N/A

Clarify this relative to a specific paragraph, sentence and page within the specification.

CE Marking Details CE Marking Provided?

Yes

State relevant hEN(s) & year

EN13964:2004+A1:2006

http://ec.europa.eu/growth/singlemarket/european-standards/harmonisedstandards/construction-products/

Date of applicability of the standard as a harmonised standard Date of the end of the coexistence period Declaration of Performance provided? (Enclose DoP, if applicable) Harmonised standard(s) & year covered by DoP

08/04/2016

08/04/2017 Yes

EN13964:2004+A1:2006

Page 1 of 4 IMS Document No: 1.04.04.01 QFC_03_PSCS

Revision: 05

Where CE marking is not available:

N/A

Supplier is to provide a letter confirming on what basis it is not available i.e. That there is no harmonised standard covering the product type etc.

Agrément Certification Irish Agrément Cert (IAB) or British Board of Agrément (BBA) provided?

No.

Note that where an IAB / BBA cert covers more than one product, the product proposed should be clearly highlighted.

Expiration date of IAB Cert

N/A

Product Data Sheet Provided?

Yes, 20EU254_DUB13 Tate HAC Submittal (GRID)

Data Sheets Note that where a Data Sheet covers more than one product, the product proposed should be clearly highlighted. List document names submitted.

Test Data or Other certification provided.

CE for Grid

Notes Product submittal for Tate Structural Ceiling Grid only.

Comments

Page 2 of 4 IMS Document No: 1.04.04.01 QFC_03_PSCS

Revision: 05

Status B comments from RKD in BLUE, Modubuild responses in RED PLEASE CONFIRM THAT THIS SUBMITTAL COMPLIES WITH THE REQUIREMENTS AS SETOUT WITHIN THE RKD SPECIFICATION IN PARTICULAR THE CEILING SYSTEMS LOADS TO BE SUPPORTED. This ceiling will support the loads as confirmed by Michael Jackson from Hanley Pepper on February 23rd 2020. PLEASE CONFIRM THAT THIS SUBMITTAL COMPLIES WITH THE AIR LEAKAGE REQUIREMENTS & dB RATINGS REQUIRED, AS SET-OUT WITHIN THE RKD SPECIFICATION IN RELATION TO THE CEILING SYSTEMS, TILES, GRIS, CLIPS, ETC. Air leakage investigation attached to submittal. Sound properties are covered in acoustic tile submittal. PLEASE CONFIRM THAT THIS SUBMITTAL COMPLIES WITH THE CEILING TILE, GRID & CLIP REQUIREMENTS, AS SET-OUT WITHIN THE RKD SPECIFICATION IN RELATION TO THE CEILING SYSTEMS. This ceiling grid submittal is provided as per the RKD specification.

Prepared on behalf of Winthrop by Name:

Emmett Gorman

Position CSA Manager / Role:

Signature:

Date: 01/03/2021

Company: WEC

Page 3 of 4 IMS Document No: 1.04.04.01 QFC_03_PSCS

Revision: 05

Submittal Review and Status ☐

Status A

Approved to Proceed



Status B

Approved with comments noted below. Comments to be addresssed & resubmitted.



Status C

Not Approved. The information supplied does not demonstrate fitness of material or the material does not fulfill the statutory requirements and/or project requirements as noted below.

Reviewer Comments - Submittal is for Tate Structural Ceiling Grid only and subject to approval of site specific details to be submitted in a separate submittal - All dimension to be checked on site prior to fabrication

Reviewer Notes

Quality Control Requirements

Reviewed by Name:

John O'Sullivan

Position / Role:

Signature: Company:

Date:

09/03/2021

RKD Architects

Page 4 of 4 IMS Document No: 1.04.04.01 QFC_03_PSCS

Revision: 05

PRODUCT APPROVAL REQUEST Issued To:

Winthorp Turnpike Business Park, Turnpike Lane, Ballymount, Dublin 22

Prepared By:

Tel:

00353 1 4600214

Tel:

Paul Devoy Modubuild Designs Ltd Unit 5, Sark Business Park, Purcellsinch Ind.Est. Dublin Rd. Kilkenny 00353 56 781 9000

Email:

[email protected]

Email:

[email protected]

Project No:

MB453

MB Issue Date:

01-03-2021

Project Name:

MSFT Dub 13

Return Date Required:

15-03-2021

Document No.

MB453-PAR-009

Revision:

1

Product Technical Submittal D Modubuild formally request your approval of the proposed products: Tate Structural Ceiling Grid Supplier: Tate Type: Structural Ceiling Grid

Please confirm your decision by ticking the appropriate box

Tick Here

Please proceed with this product – No Comments

☐ ☐ ☐

Please proceed with this product – With Comments Please DO NOT proceed with this product Reason for non-approval where applicable or comments:

SIGNATURE:

…………………………………………………

DATE:

………………………………………

NOTE: Approval of a product submittal supersedes all previous submissions and correspondences relating to that product.

QF 8.01-03

Data & Flooring Technology Structural Ceiling Solutions Europe

Submittal Pack Tate Grid Project Reference: 20EU254_DUB13_TateGrid_Submittal

Tate Grid Metric Tate Grid GRID SPECIFICATIONS

Field Connector for simple installation

M10-1.5 Turnbuckle connections to structural steel Main Runner with location notches

Floating Perimeter detail

Structural Tee with coped ends

CONNECTOR SPECIFICATIONS

Field-Cut Perimeter Connector

• High Strength Cast Aluminum Construction • Corrosion Resistant Aluminum Casting • Ribs on connector to engage with grid and prevent racking • Attaches to grid members with (4) 1⁄4”-20 screws • M10-1.5 Turnbuckles with starter rod threads into connectors on a 1200x1200mm spacing • On site modifiable connectors for perimeter installation

50.8mm

50.8mm

COMPONENTS Field Connector

30mm

Perimeter Extrusion

• Pre-engineered and factory produced aluminum structural ceiling grid with continuously threaded slot • Grid consists of Main Runners with notches for precise location and connection of coped Structural Tees using simple four screw connectors • Capable of supporting power modules, light fixtures, cable trays, partitions, and other accessories • Load performance based on building connection spacing of 1200mm on center • Max grid point load at midspan of 1.7 kN • Max grid uniform load of 2.4 kN/m2 • Safety factor of 2 for all connections • Grid member center to center spacing can be selected to accommodate project specific specs. (see page 3 for more information)

39.6mm

Mains and Structural Tees

Perimeter & XL Connector

• 3600mm Main Runner / 3600mm Perimeter Angle • 600mm Structural Tee / 1200mm Structural Tee • Field Connector / XL Connector • Perimeter Connector • 1⁄4”-20 x 1-1⁄4” Screws w/ 1⁄4” Lock washer • M10-1.5 x 178mm Turnbuckle Assembly with Starter Rod • Ceiling Hold Down Clips (optional) • Factory Applied Gasket (optional) • Ceiling Tiles & Lights (supplied by others) • Threaded Rod Connection to Building (supplied by others)

GRID OPTIONS Grid Color ☐ White Paint

☐ Black Paint

☐ Clear Anodized

Grid Thread Pattern – Bottom Slot ☐ M10-1.5 ☐ 3⁄8”-16 ☐ 1⁄4”-20 ☐ 1⁄4”-20 Hidden Slot

Simple supported 4 screw assembly and vertically supported fl anged grid

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

Pre-threaded connections for cable trays, utilities and other accessories

Rev - 08/12/16

Grid Spacing – On center (see page 3 for detail) ☐ 600 x600mm ☐ 600 x 1200mm ☐ 610 x 610mm ☐ 610 x 1210 ☐ 613 x 613mm ☐ 613 x 1213mm ☐ Other © 2016 Tate Access Floors, Inc. 1 of 9

Tate Grid Metric Tate Grid PROFILE OPTIONS

M10 Bottom Slot*

⁄8”-16 Bottom Slot*

3

10.4

10.4

• 19.1

⁄4”-20 thread

1



50.8

• 20.1

⁄4”-20 thread

Continuous threaded M10-1.5 bottom slot

Continuous threaded top slot

1/4”-20

19.1

1



M10-1.5 RH thread

Continuous threaded 1/4”-20 top slot



Continuous threaded slot

3/8”-16 bottom

Utilizes standard hardware connectors and features of Tate Grid

50.8



⁄8”-16 RH thread

3

20.3

14.2

Utilizes standard hardware connectors and features of Tate Grid

13.2 12.7

13.2

3.2

39.6

3.2

39.6

⁄4”-20 Slot*

⁄4”-20 Hidden Slot*

1

1

10.4

10.4

19.1

1

⁄4 ”-20 thread



Continuous threaded 1/4”-20 slots on top and bottom



Utilizes standard hardware connectors and features of Tate Grid

Continuous threaded 1/4”-20 slots on top and bottom



Bottom 1/4”-20 slot is hidden, can be exposed by drilling through bottom wall cover



Utilizes standard hardware connectors and features of Tate Grid

19.1

⁄4”-20 thread

1

50.8

50.8

19.1

19.1 14.7

14.7



3.2

3.2

39.6

39.6

⁄4”-20 Perimeter*

1

Light Structural Extrusion* 9.9

10.4



1

⁄4”-20 thread

• 50.8

• 16.8

6.4

39.6

3.2

Continuous threaded 1/4”-20 top slot

⁄4”-20 thread

1

Utilizes standard hardware connectors and features of Tate Grid For infill applications where complete mounting flexibility across the ceiling is not required



Continuous threaded 1/4”-20 top slot



Intended for fixed perimeter installation areas (See page 6)



Utilizes all standard hardware connectors and features of Tate Grid

50.8

14.7

3.2

30

*Note: All Dimensions are in Millimeters

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 2 of 9

Tate Grid Metric Tate Grid GRID SPACING AND TILE SIZING Center-on-Center Grid Spacing

Inside Grid Dimension Tile size

If you want the Grid Spacing to be on a 600 x 600mm or 600 x 1200mm module size, use this table to determine tile size requirement: Grid Profile 1

⁄4”-20 Bottom Slot & ¼”-20 Hidden Slot

M10-1.5 & 3⁄8 ”-16 Bottom Slot

Grid Spacing (L x W)

Tile Size (L x W)

600 x 600mm

582 x 582mm +/- 4mm

600 x 1200mm

582 x 1182mm +/- 4mm

600 x 600mm

580 x 580mm +/- 3mm

600 x 1200mm

580 x 1180mm +/- 3mm (see example below)

Note: Maximum Tile Size = Inside Grid Dimension minus 3.2mm. Minimum Tile Size is based on a minimum overlap on the extrusion flange of 3.2mm when the tile is shifted all the way to one side.

If you want the Grid Spacing to be on a larger module size to fit standard 600 x 600mm or 600 x 1200mm nominal tile sizes, use this table: Grid Profile 1

⁄4”-20 Bottom Slot & ¼”-20 Hidden Slot

M10-1.5 & 3⁄8 ”-16 Bottom Slot

Grid Spacing (L x W)

Tile Size (L x W)

610 x 610mm

593 x 593mm +/- 4mm

610 x 1210mm

593 x 1193mm +/- 4mm

613 x 613mm 613 x 1213mm

593 x 593mm +/- 4mm 593 x 1193mm +/- 4mm (see example below)

Note: Maximum Tile Size = Inside Grid Dimension minus 3.2mm. Minimum Tile Size is based on a minimum overlap on the extrusion flange of 3.2mm when the tile is shifted all the way to one side.

Sizing Based on 600 x 1200mm Grid Spacing

Sizing Based on 600 x 1200mm Nominal Tile Size 593mm

580mm

1193mm

1180mm

1213mm

1200mm

600mm

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

613mm

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 3 of 9

Tate Grid Metric Tate Grid PERFORMANCE CRITERIA The bottom side of the structural grid is available with an M10-1.5, 3⁄8”-16, or 1⁄4”-20 continuous threaded slot for mounting items directly to the grid. Refer to the table below for load performance details on the grid and connections. Structural Tee Defl ection (Midspan Beam)

1200mm 600mm

Load

Ultimate Load = 3.1 kN

Calculate midspan beam defl ection at any point below yield

Deflection (mm)

30

S=

24

Wl 3 48EI

S = Deflection W = load l = 1200mm

E = 68.9 kN/mm2 I = 63700mm4

18 12

Yield Point = 1.7 kN

6

Load (kN)

System Performance Criteria

Hanging Method

Grid Load Performance (with building connections 1200mm x 1200mm on centers)

Connection to Bottom Slot (3⁄8”-16 or 1⁄4”-20)

Connector to Grid

1.7 kN*

1.7 kN*

3.6 kN*

2.4 kN/m2

-

-

3.1 kN

3.4 kN

7.2 kN

Point Load (kN) Uniform Load (kN/m2) Ultimate Point Load (kN) *Max point load no less than 1200mm apart in any direction.

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 4 of 9

Tate Grid Metric Tate Grid FIELD CONNECTOR ASSEMBLY

Structural Tee coped for simplified installation and stronger connections

Ribs on connector to align with grid and prevent racking

Main Runners notched to positively position connectors on center every time

XL CONNECTOR

Main Runner Notch

XL Connector is designed for additional support at the ends of each Main Runner.

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 5 of 9

Tate Grid Metric Tate Grid PERIMETER CONNECTOR

Perimeter Connector can be cut on site to be used in various locations to connect grid together.

Bottom of Perimeter Connector is designed with ribs that locate the connector on Perimeter Extrusion.

MAIN RUNNERS AND STRUCTURAL TEES 600mm nominal

All 600mm and 1200mm Structural Tees have coped ends which allows the grid to rest on the longer sections for stronger connections and simplified installation. 600mm nominal

600mm nominal

All 1200mm Structural Tees and Main Runners are notched every 600mm on center for proper alignment and spacing of the connectors.

600mm nominal

600mm nominal

3600mm Note: Structural Tee and Main Runner dimensions are nominal and are adjusted for custom-sized ceiling grid designs Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 6 of 9

Tate Grid Metric Tate Grid PERIMETER ANGLES

XL Connector (Field-Cut) for Floating Installation Perimeter Connector

Main Runner

Wall Angle (By Others)

Perimeter Angle

Floating Installation Detail

Fixed Installation Detail

Main Runners are utilized when installing with a floating detail. When installing with a floating perimeter, XL Connectors can be utilized to take advantage of the notches and ribs that align extrusions and prevent racking.

Perimeter Extrusions are designed to create a clean corner joint assembly. Perimeter Angles can be cut on site to desired length when assembled along perimeter walls. Perimeter Angles can also be bolted directly to the wall with appropriate fasteners for wall type.

Additionally it is recommended to utilize a Wall Angle attached to the perimeter.

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

Note, pre-drilling is recommended and through holes are suggested for simpler light fixture or drop ceiling tile installation.

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 7 of 9

Tate Grid Metric Tate Grid 600 X 600mm CEILING GRID WITH 1200 X 1200mm TURNBUCKLE LAYOUT AND FIXED PERIMETER

3 3

1

8 4

1

5 7 6

2 2

3600mm

1 Main Runner

1200mm

5 Structural Tee

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

2

6

3600mm Perimeter Angle

3 Field Connectors

4 XL Connector

600mm Structural Tee

7 Perimeter Connectors

8 Turnbuckle Assembly

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 8 of 9

Tate Grid Metric Tate Grid TURNBUCKLE ASSEMBLY

Internally Threaded Anchor (Supplied by others)

RH M10-1.5 Threaded Rod and connection to decking (Supplied by others)

M10-1.5 LH/RH x 178mm Turnbuckle

M10-1.5 Threaded Starter Rod into Turnbuckle

M10-1.5 RH Threaded Connection to Field Connector

Tate Access Floors, Inc. 7510 Montevideo Road Jessup, MD 20794 Tel (410)799-4200

Rev - 08/12/16

© 2016 Tate Access Floors, Inc. 9 of 9