Durga Site : M/S CHESLIND TEXTILES LTD Test Report Switchgears B.MADUGANAPALLI, Page No: 1a BAGALUR – 635 103. HOSUR TALUK. LOCATION : OUTDOOR Date: 14 th January 2016. FEEDER NAME : 33KV YARD INCOMER SERIAL NUMBERS : R PHASE - A 16673 MAKE : INTRANS ENGG. Y PHASE - A 16674 CORE 1 : CT RATIO : 150 /...
Durga Switchgears Site : M/S CHESLIND TEXTILES LTD B.MADUGANAPALLI, BAGALUR – 635 103. HOSUR TALUK. Test Report Page No: 1a LOCATION : OUTDOOR Date: 14th January 2016. FEEDER NAME : 33KV YARD INCOMER SERIAL NUMBERS : R PHASE - A 16673 MAKE : INTRANS ENGG. Y PHASE - A 16674 CORE 1 : CT RATIO : 150 / 1 AMP B PHASE - A 16675 15 VA, CL 1 CORE 2 : CT RATIO : 150/1 AMP 15 VA, CL 5P10 ILV : 36/ 70 / 170 KV (Insulatin Level Viltage PRIMARY INJECTION TEST REPORT FOR CURRENT TRANSFORMER PRIMARY TERMINAL TIGHTNESS : SATISFACTORY SECONDARY TERMINAL TIGHTNESS : SATISFACTORY POLARITY TEST : OK RATIO TEST: CORE 1 - METERING CORE 2 - PROTECTION IR Value Test: Primary to Earth – 500 M Primary to Core 1- 900 M Primary to Core 2 - 600 M Core 1 to earth – 500 M Core 2 to earth - 500 M Current Injected in %age current in Amps Calculated secondary current in Amps Actual secondary current in Amps R-Phase Y-Phase B-Phase 20% 30 0.20 0.19 0.19 0.21 40% 60 0.40 0.40 0.40 0.40 60% 90 0.60 0.61 0.61 0.61 80% 120 0.80 0.81 0.79 0.79 100% 150 1.00 0.99 1.00 1.01 Current Injected in %age current in Amps Calculated secondary current in Amps Actual secondary current in Amps R-Phase Y-Phase B-Phase 20% 30 0.20 0.21 0.20 0.21 40% 60 0.40 0.39 0.39 0.40 60% 90 0.60 0.61 0.60 0.60 80% 120 0.80 0.81 0.80 0.80 100% 150 1.00 1.00 1.00 0.99...