BLDG 471 HVAC Design Air Distribution System Design Notes...
1
Duct Layout, Diffuser and Return Air Grille Placement
BLDG 471
Dr. M. Zaheeruddin
Fall 2021
2
Diffuser Selection/Placement VT (terminal velocity): the value in fpm that exists at the end of the throw (T) from the diffuser. T VT Vk
T: throw (ft) Vk: outlet velocity (fpm) VT: terminal velocity (fpm) VR: room velocity (fpm)
VR Three different range of terminal velocities are normally given in catalogue: T
VR Recommended use: VT
50 ft/min
when people are located adjacent to the walls,
VT
100 ft/min
when people are not located adjacent to the walls, such as in stores and restaurants
VT
150 ft/min
when people are not at all located adjacent to the walls
A specification of 3-4-5 feet means a throw at three different velocities such as @150’
100’
50’
ADPI: Air distribution performance index ADPI is defined as the percentage of measurements taken at many locations is the occupied zone of a space that meet -3 to 2F effective draft temperature (EDT) criteria [where EDT is the difference between any point in occupied space and control condition ] 𝐸𝐷𝑇 = (𝑡𝑎 − 𝑡𝑟 ) − 𝑀(𝑉𝑥 − 𝑉𝑟 ),
where 𝑉𝑟 = 30
BLDG 471
𝑓𝑡
𝑚𝑖𝑛
, 𝑎𝑛𝑑 𝑀 𝑖𝑠 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡 = 0.07 𝐹 ∙ 𝑚𝑖𝑛/𝑓𝑡
Dr. M. Zaheeruddin
Fall 2021
3
Diffuser Selection (Ceiling Diffuser) Given: -
cfm=250,
-
Load = 8000BH or load/ft2=36BH/ft2
Step1: For a known diffuser type and room size, determine the characteristic length (distance to closest wall, (Table 11-1) Step 2: select throw-to-length ratio for max ADPI (Table 11-2) Step 3: Calculate throw and select appropriate diffuser from the catalogue data. Solution:
Characteristic length: 7’ (minimum value) From Table 11-2, for 36BH/ft2 load ≈40:
BLDG 471
X50/L = 0.8
for 88% ADPI
X50/L = 0.5 – 1.5
for 80% ADPI
Dr. M. Zaheeruddin
Fall 2021
4
To achieve 50 terminal velocity: The required throw = 0.8*7 = 5.6’
for 88% ADPI
The required throw = 1.5*7 = 10.5’
for min. 80% ADPI
From catalogue (Table 11-4) for ceiling diffusers select a diffuser. Check the 10“ diffuser: 10” Ø between 220cfm/270cfm will this be adequate?
Check ΔP0 and throw:
0.027 𝑖𝑛 𝑊𝐺 0.043 𝑖𝑛 𝑊𝐺 ( 150′ 100′ 50′ ) ⟨ 7′ → 3 − 4 − 7 8′ → 3 − 5 − 8
∆𝑃0 ⟨ ∆𝑃0
Find ΔP0 for 250 cfm:
𝑄
𝑄𝑟𝑎𝑡𝑒𝑑
=(
1/2
∆𝑃0 ) ∆𝑃0 𝑟𝑎𝑡𝑒𝑑
250 2 ) ∗ 0.043 = ( ) ∗ 0.043 = 0.0341 " 𝑊𝐺 ∆𝑃0 = ( 𝑄𝑟𝑎𝑡𝑒𝑑 270 𝑄
2
𝑇 = 𝑏𝑒𝑡𝑤𝑒𝑒𝑛 7 − 8′
BLDG 471
Dr. M. Zaheeruddin
Fall 2021
5
؞Diffuser specifications: ▪
10ӯ ceiling (round) diffuser
▪
ΔP0 = 0.035” WG
▪
T = 7-8 ‘
▪
NC = 11 (Table 11-4)
NC in offices
25-30
NC in classroom
25-30
BLDG 471
Dr. M. Zaheeruddin
Fall 2021...