Abb acs800 replace fan - PLCS.net - Interactive Q & A

You are not registered yet. Please click here to register!

This board is for PLC Related Q&A ONLY. Please DON'T use it for advertising, etc. Try our online PLC Simulator- FREE. Click here now to try it.

New Here? Please read this important info!!!

PLCS.net - Interactive Q & A > PLCS.net - Interactive Q & A > LIVE PLC Questions And Answers

FAQ

Calendar

Downloads

Remember Me? Log in

Password

Abb acs800 replace fan Register

User Name User Name

PLC Reviews

PLCS.net Store

Today's Posts

Search

Page 1 of 2 1 2 > Thread Tools

Display Modes

April 21st, 2014, 07:25 AM

#1

geoplc

Abb acs800 replace fan

Member

anyone KNOW THE MAINT CODE TO RESET THE "REPLACE FAN" HOURS RUN REGISTER IN ACS800 DRIVE. DID IT FEW YEARS BACK BUT CANT REMEMBER.

Join Date: Oct 2006 Location: PAinesville OH Posts: 123

April 21st, 2014, 07:39 AM

osmanmom

#2

01.44-16.12

Member

Join Date: Mar 2014 Location: JOHOR Posts: 1,454

April 21st, 2014, 09:20 AM

geoplc Member www.plctalk.net/qanda/showthread.php?t=86998

#3

Ok Im a little rusty. I know 1.44 is the fault code for the fan hour limit, but dont remember the significance of 16.12 and how I went 1/6

7/7/2021

Abb acs800 replace fan - PLCS.net - Interactive Q & A

You are not registered yet. Please click here to register!

Join Date: Oct 2006 Location: PAinesville OH Posts: 123

April 21st, 2014, 09:27 AM

osmanmom Member

#4

Abc Attached Images ABC.jpg (21.8 KB, 412 views)

Join Date: Mar 2014 Location: JOHOR Posts: 1,454

April 22nd, 2014, 09:10 AM

geoplc Member

#5

Sorry about delay, parameter 16.12 is not accessible on the keypad control, only goes to 16.11. I vaguely remember having to enter a pass code in order to do this. Supposedly it can be reset using drivewindow software which i believe we may still have. Will look into further.

Join Date: Oct 2006 Location: PAinesville OH Posts: 123

April 22nd, 2014, 09:26 AM

osmanmom Member

Join Date: Mar 2014 Location: JOHOR Posts: 1,454

#6

Actually it depend your Firmware Manual User, Inline,Crane,Fan Pump,Extruder,Traverse,IGBT all have their Firmware manual user. The reset counter will different 16.11-16.12-16.09 base on Firmware manual. i give you default ACS800 Standard Manual User, the important thing your Manual User must keep at proper place

September 30th, 2015, 08:44 AM

Cphe747 Member

Join Date: Sep 2015 Location: Newcastle Posts: 4

www.plctalk.net/qanda/showthread.php?t=86998

#7

We have some ASC800 drives running on our plant. Some of them have recently gave Alarm Messages on the Control Panel which says: Replace Fan(4280) I did replace the cooling fan with one from our spare drives. My problem is the fact that Parameter 16.12 which is used to reset the cooling fan run time counter is not accessible on the control panel. Is there any method to reset this counter either than using the PC Tool? Is there a pass key or anything that can enable me to view the Parameter 16.12 and 01.44 etc? 2/6

7/7/2021

Abb acs800 replace fan - PLCS.net - Interactive Q & A

You are not registered yet. Please click here to register!

September 30th, 2015, 05:42 PM

DickDV Member

#8

Why not give ABB Tech Service a call----800.752.0696 Option 1 and Option 1. Knowledgeable friendly people during business hours in Milwaukee WI and NO CHARGE!

Join Date: May 2002 Location: Kalamazoo MI Posts: 2,324

October 1st, 2015, 12:37 AM

Cphe747 Member

Join Date: Sep 2015 Location: Newcastle Posts: 4

#9 Quote:

Originally Posted by DickDV Why not give ABB Tech Service a call----800.752.0696 Option 1 and Option 1. Knowledgeable friendly people during business hours in Milwaukee WI and NO CHARGE! I will do that, thank you very much

November 20th, 2015, 02:44 AM

Wizlock

#10

Did you get anywhere on this? Having the same problem.

Member

Join Date: Aug 2014 Location: Western Norway Posts: 17

November 20th, 2015, 03:10 AM

Cphe747 Member

Join Date: Sep 2015 Location: Newcastle Posts: 4

#11 Quote:

Originally Posted by Wizlock Did you get anywhere on this? Having the same problem. Good day, unfortunately I did not come right. I have 20 of these drives. ABB South Africa says I have to send the drives to them or bring their technician onsite which is not practical. Sorry

May 26th, 2016, 08:58 AM

Milspecelectrician Member

www.plctalk.net/qanda/showthread.php?t=86998

#12

SOLUTION Okay so I made this account JUST to reply and solve this problem for everyone... 3/6

7/7/2021

Abb acs800 replace fan - PLCS.net - Interactive Q & A

You are not registered yet. Please click here to register!

Join Date: May 2016 Location: Canada Posts: 1

Go to parameter 16-03 -enter 2303 as passcode -press enter -"..." Should appear for a brief moment Go to parameter 145 (yes 145 now exists, before it only went to 99) -go to sub-parameter 13 Titled "FAN ON-TIME" -Press enter -now you must hold the down arrow until you have brought the hours down to zero. This will take some time as it only decreases in increments of 10, my counter is at 50 000+ -once back to zero press enter. Problem solved, drive should run immediately if being called on to start Go to parameter 16-03 again -Press enter -enter 358 as passcode -press enter Now you are done. ACT button out and let fly!

Hope this helps everyone reading this in the future

May 26th, 2016, 09:19 AM

Pete.S. Member

Join Date: Mar 2016 Location: Fl Posts: 464

#13 Quote:

Originally Posted by Milspecelectrician SOLUTION Okay so I made this account JUST to reply and solve this problem for everyone... To reset the fan counter do as follows Go to parameter 16-03 -enter 2303 as passcode -press enter -"..." Should appear for a brief moment Go to parameter 145 (yes 145 now exists, before it only went to 99) -go to sub-parameter 13 Titled "FAN ON-TIME" -Press enter -now you must hold the down arrow until you have brought the hours down to zero. This will take some time as it only decreases in increments of 10, my counter is at 50 000+ -once back to zero press enter. Problem solved, drive should run immediately if being called on to start Go to parameter 16-03 again -Press enter -enter 358 as passcode -press enter Now you are done. ACT button out and let fly! Hope this helps everyone reading this in the future

www.plctalk.net/qanda/showthread.php?t=86998

4/6

7/7/2021

Abb acs800 replace fan - PLCS.net - Interactive Q & A

You are not registered yet. Please click here to register!

May 26th, 2016, 08:27 PM

#14

Interesting- does the VFD actually prevent the drive from starting when the fan run-hours reach a certain limit? Or does it just alarm?

rupej Member

Join Date: Sep 2014 Location: NC Posts: 857

June 16th, 2016, 12:00 PM

ranjankamath Member

#15

Thanks for your Post,can you please share ACS 800 Manual containing Parameter Description for Group 145

Join Date: Oct 2010 Location: Mysore Posts: 1

Page 1 of 2 1 2 >

Jump to Live PLC Question and Answer Forum Bookmarks Twitter

Reddit

Digg

del.icio.us

StumbleUpon

Google

« Previous Thread | Next Thread »

Currently Active Users Viewing This Thread: 1 (0 members and 1 guests)

Posting Rules You You You You

may may may may

not not not not

post new threads post replies post attachments edit your posts

BB code is On Smilies are On [IMG] code is On HTML code is Off Forum Jump LIVE PLC Questions And Answers

Forum Rules

Go

Similar Topics Thread

www.plctalk.net/qanda/showthread.php?t=86998

Thread Starter

Forum

Replies

Last Post

5/6

7/7/2021

Abb acs800 replace fan - PLCS.net - Interactive Q & A

You are not registered yet. Please click here to register!

ABB ACS800 & Ethernet

Elcan

LIVE PLC Questions And Answers

5

May 20th, 2013 11:06 AM

ABB ACS800 Drive

Rob S.

LIVE PLC Questions And Answers

8

March 19th, 2013 06:00 PM

ABB RETA-01 to ACS800 firmware compatibility

Purrdie

LIVE PLC Questions And Answers

3

October 24th, 2011 11:02 PM

ABB ACS800 LC firmware

TOKG1Tech

LIVE PLC Questions And Answers

3

June 14th, 2011 09:13 PM

ABB ACS800 A1>min Fault (8110)

thebuzz

LIVE PLC Questions And Answers

9

May 14th, 2011 10:13 AM

All times are GMT -4. The time now is 02:47 PM. -- PLCS.net - Interactive Q & A Normal Style

Contact Us - PLCS.net - Text - Top .

www.plctalk.net/qanda/showthread.php?t=86998

6/6...