Operating Instructions
Searchpoint Optima Plus with optional HART® output
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
Revision History Revision
Comment
Date
Issue 6
A04544
May 2015
Issue 7
A05004
July 2017
2
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
1. Safety Warnings and Information WARNINGS 1.
Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned. For Europe see EN60079-14, EN60079-29-2, and EN61241-14. For installations in North America, the National Electrical Code (NFPA 70) should be strictly observed. Elsewhere the appropriate local or national regulations should be used.
2.
Searchpoint Optima Plus is designed for installation and use in Zone 1 or 2 hazardous areas (International) and for Class 1 Division 1 or 2 area applications (North America).
3. Donotmodifyoraltertheconstructionoftheproductasessentialsafetyandcertification requirements may be invalidated. 4.
In order to maintain electrical safety, the product must not be operated in atmospheres with more than 21% oxygen.
Cautions During usage, as some test gases may be hazardous, outlets from gassing accessories should exhaust to a safe area. UseoftheSearchpointOptimaPlusoutsideofthespecifiedrangeofoperatingconditionswillinvalidate certificationandproductapproval. CSA performance approval only covers the gas detection function.
Special Conditions of Use InordertocomplywiththeATEXCertification,thefollowingspecialconditionsofusemustbeadheredto:1.
The integral supply cables must be mechanically protected and terminated in a suitable terminal or junction facility.
2. ThecoverfixingscrewsshallbestainlesssteelgradeA4-80minimum(onlyuseHoneywellsupplied screws).
3
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
Contents Section
Page
1.
SAFETY WARNINGS AND INFORMATION 1.1 HOWTOUSETHISMANUAL 1.2 BATTERIES
2 7 8
1.3
DISPOSAL 1.3.1 SearchpointOptimaPlus 1.3.2 Packaging
8 8 8
1.4
INFORMATION
9
2
INTRODUCTION 2.1 SEARCHPOINTOPTIMAPLUS
9 10
2.2 2.3 2.4
SEARCHPOINTOPTIMAPLUSOPTIONS TERMINATION UNIT OPTIONS COMMISSIONINGANDMAINTENANCETOOLS
11 12 13
2.5
WEATHERPROTECTIONACCESSORIES
13
2.6 2.7
GASSING ACCESSORIES MOUNTING ACCESSORIES
14 15
MECHANICALINSTALLATION 3.1 SITING 3.2 INSTALLATION 3.2.1 StandardInstallation
17 17 17 18
19 20
3
4
5
7
Installationwithaflowhousing(samplingsystem) Sampling system using Remote Gassing Cell (RGC)
3.2.4
Installation in a duct
20
3.2.5 Installation of gassing pipes for Remote Gassing Cell ELECTRICALINSTALLATION
23 24
4.1
POWERSUPPLY
24
4.2
CABLINGRECOMMENDATIONS
25
4.3 4.4
EARTHREGIMES CONNECTIONS
25 27
OPERATION 5.1 DEFAULTCONFIGURATION 5.2
6
3.2.2 3.2.3
29 29
HART®OPERATIONDURINGFAULT
29
COMMISSIONING 6.1 FIRSTTIMESWITCHON MAINTENANCE
30 30 31
7.1
INTRODUCTION
31
7.2 7.3
INSPECTION INSPECTIONOFAUNITFITTEDWITHAFLOWHOUSING
31 31
7.4
BUMPTEST(GASCHALLENGE)
32
7.5
BUMPTEST(GASCHALLENGE)WITHREMOTEGASSINGCELL(RGC)
33
4
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
Contents 8
USEOFTHESHC1HANDHELDINTERROGATOR
34
8.1
INTRODUCTION
34
8.2 8.3
SHC1CONNECTION SHC1OPERATION
34 36
8.4
STATUS INDICATION
37
8.5
SHC1BATTERYREPLACEMENT
9
COMMISSIONINGUSINGSHC1HANDHELDINTERROGATOR
10
11
37 38
9.1
INTRODUCTION
38
9.2 9.3
FIRSTTIMESWITCHON CLEARFAULTSORWARNINGS
38 39
9.4
FIXTHE4-20MAOUTPUT
39
9.5
TEST4-20MALOOPINTEGRITY
40
MAINTENANCEUSINGSHC1HANDHELDINTERROGATOR 10.1 INTRODUCTION
41 41
10.2 10.3 10.4
INSPECTION INSPECTIONOFAUNITFITTEDWITHAFLOWHOUSING BUMPTEST(GASCHALLENGE)
41 42 43
10.5
BUMPTEST(GASCHALLENGE)WITHREMOTEGASSINGCELL(RGC)
43
10.6
RE-ZEROSEARCHPOINTOPTIMAPLUS
44
10.7
CALIBRATION
45
10.8 INVESTIGATIONOFFAULTSORWARNINGS USEOFTHEHART® COMMUNICATIONS
46 47
11.1
GENERAL
47
11.2 11.3
CONNECTION SEARCHPOINTOPTIMAPLUS USER INTERFACE 11.3.1 AccessLevelsandPasswordProtection
47 47 47
11.3.2 11.3.3
48 50
12
11.3.4 Error Reporting COMMISSIONINGUSINGHART® COMMUNICATIONS
50 51
12.1 12.2 12.3
INTRODUCTION FIRSTTIMESWITCHON USER CONFIGURATION
51 52 52
12.3.1 12.3.2
Change the Password ConfigureHART® Operation during Fault
52 53
12.3.3 12.3.4
Set the Time and Date ConfigureWarning,InhibitandOverrangeSignalLevels
53 54
12.4 12.5 12.6
CONFIGURE DEVICE IDENTIFICATION INFORMATION FIXTHE4-20MAOUTPUT TEST4-20MALOOPINTEGRITY
MenuStructure Menu Navigation
12.7 CALIBRATETHE4-20MALOOP 12.8 CONFIGUREINTERNALALARMTHRESHOLD 12.9
SIMULATION
54 55 56 56 57 57
12.10 CLEARFAULTSORWARNINGS
58 5
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
Contents 13
MAINTENANCEUSINGHART® COMMUNICATIONS 13.1 INTRODUCTION
60 60
13.2 13.3
INSPECTION INSPECTIONOFAUNITFITTEDWITHAFLOWHOUSING
60 61
13.4
BUMPTEST(GASCHALLENGE)
62
13.5 13.6
BUMPTEST(GASCHALLENGE)WITHREMOTEGASSINGCELL(RGC) RE-ZEROSEARCHPOINTOPTIMAPLUS
63 64
13.7
CALIBRATION
64
13.8 STORECALIBRATIONINFORMATION 13.9 INVESTIGATIONOFFAULTSORWARNINGS
65 66
14
PROBLEMSOLVING
67
14.1
TROUBLESHOOTING
67
14.2
WARNINGANDFAULTMESSAGES
71
14.3 FURTHERASSISTANCE SPECIFICATIONS
72 73
15.1 15.2
SPECIFICATIONS AVAILABLEGASCALIBRATIONS
73 74
15.2.1
16 17 18
15.2.2 Ethylene version of Searchpoint Optima Plus 15.3 CROSSINTERFERENCETOOTHERGASESANDVAPOURS ORDERING INFORMATION WARRANTY SUMMARY CERTIFICATIONANDAPPROVALS
77 78 79 82 83
18.1 ECDECLARATIONOFCONFORMITY
83
18.2 HAZARDOUSAREACERTIFICATION
83
18.2.1
ATEX
83
18.2.2 18.2.3
UL InMetro(Brazil)
83 83
18.2.4
CSA
84
18.2.5
FM
84
18.2.6 18.2.7
CU-TREx(Eurasian)Approval–XTCVersion CCCF(China)
84 84
18.2.8 IECEx 18.3 PERFORMANCEAPPROVALS 18.3.1 ATEX
84 84 84
18.3.2
FM
85
18.3.3
RussianPatternApproval(Metrology)-XTCVersion
85
18.4 MARINEAPPROVALS 18.5 SHC1HANDHELDINTERROGATORHAZARDOUSAREACERTIFICATION
86 86
19
18.5.1 ATEX 18.5.2 IECEx APPENDIX1–SHC1ADDITIONALFUNCTIONS
86 86 87
15
HydrocarbonversionofSearchpointOptimaPlus
74
19.1
CHANGINGTHETARGETGAS
87
19.2
SELFTEST
88 6
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
Contents 20
APPENDIX2–HART®ADDITIONALFUNCTIONS
89
21
20.1 CHANGINGTHETARGETGAS 20.2 SETHART®LOOPCURRENTMODE APPENDIX3–SPECIALNOTESFORHONEYWELLMCTOOLKITUSERS
89 91 92
22
APPENDIX4–ENDOFLIFEBATTERYREMOVAL
93
23
APPENDIX5-HART COMMANDS USED 23.1 UNIVERSALCOMMANDS 23.2 COMMON-PRACTICE COMMANDS
94 94 94
®
23.3
23.2.1
Supported Commands
94
23.2.2 23.2.3
Burst Mode Catch Device Variable
94 94
DEVICE-SPECIFIC COMMANDS
95
7
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
1. Safety Warnings and Information 1.1 How to use this manual This manual contains three sets of instructions for Searchpoint Optima Plus - as a stand alone unit, when usingtheSHC1HandheldInterrogatorandwhenusingtheHART® communications. Use the guide below to findtherelevantchapters:Stand alone unit Chapters 1-5
Chapters 6-7 Chapters14-16
Introduction, Installation and Operation Commissioning and Maintenance ProblemSolving,SpecificationandCertification
With SHC1 Handheld Interrogator Chapters 1-5 Introduction, Installation and Operation Chapters8-10 UseofSHC1,CommissioningandMaintenance
Chapters14-16 Appendix 1
ProblemSolving,SpecificationandCertification Additional Functions
With HART® communications Chapters 1-5 Introduction, Installation and Operation Chapters11-13 UseofHART®, Commissioning and Maintenance
Chapters14-16
ProblemSolving,SpecificationandCertification
Appendix 2
Additional Functions
Searchpoint Optima Plus with XNX Universal Transmitter When using Searchpoint Optima Plus with the XNX Universal Transmitter, this manual and the XNXUniversalTransmittermanualarerequired.Therelevantchaptersofthismanualare:-
Chapters 1-4
Introduction and Installation
Chapter 7 Chapters14-16
Maintenance ProblemSolving,SpecificationandCertification
For Commissioning and Operation please use the XNX Universal Transmitter manual (part number 1998M0738). TheXNXUniversalTransmitterhasitsownintegralHART® communications and will not re-transmit the Searchpoint Optima Plus communications. Please refer to the XNX Universal Transmitter manual for the appropriateHART® commands and menu structure. Note:ThismanualisforusewithSearchpointOptimaPlusunitsofmodstate9andabove. Note:Translationsofthismanualinvariouslanguagesareavailable,eitherontheCDaccompanyingthe product or at our website. Navigate to www.honeywellanalytics.com and use the Document Download utility. It may be necessary to register to view all of the available documents.
8
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
1. Safety Warnings and Information 1.2 Batteries Belowisalistingofbatteriespresentintheproductscoveredbythismanual: Battery Description
Battery Type
Location
Replaceable
Alkaline
SHC1 Handheld Interrogator
Yes
Lithium Manganese Dioxide
Searchpoint Optima Plus
No
Size 6LR61 (PP3) Size CR2032
Batteries contain various active ingredients which store electrochemical energy and can be dangerous if they contact your skin. Removal and Disposal Information: The product documentation includes instructional information of the proper removal of thebatteriesusedintheseproducts(Section8.5andAppendix4).Thesymbolleftmeans that according to local laws and regulations the battery installed within your product should be disposed of separately from household waste. When the battery reaches its end of life, take it to a collection point designated by local authorities.
1.3 Disposal 1.3.1 Searchpoint Optima Plus When Searchpoint Optima Plus reaches the end of its life it should be disposed of in accordance with local regulations. SearchpointOptimaPlusconsistsofthefollowingtypesofmaterials:• Stainless steel • Various epoxy resins • Various glasses • Various engineering plastics • Various rubbers • Printed circuit boards See Appendix 4 for instructions on battery removal.
1.3.2
Packaging
Searchpoint Optima Plus packaging is made from cardboard. Facilities for recycling are widely available.
9
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
1. Safety Warnings and Information 1.4 Information This manual is for use with Searchpoint Optima Plus, Searchpoint Optima Plus XTC, Searchpoint Optima X and Searchpoint Optima Z units of mod state 9 and above. For Searchpoint Optima X and Searchpoint Optima Z please also refer to the supplementary information sent with the product. HoneywellAnalyticscantakenoresponsibilityforinstallationand/oruseofitsequipmentifnotdonein accordancewiththeappropriateissueand/oramendmentoftheOperatingManual. The reader of this Operating Manual should ensure that it is appropriate in all details for the exact equipmenttobeinstalledand/oroperated.Ifindoubt,contactHoneywellAnalyticsforadvice. ThefollowingtypesofnoticesareusedthroughoutthisOperatingManual:
WARNING Identifiesahazardousorunsafepracticewhichcouldresultinsevereinjuryordeathtopersonnel.
Caution: Identifies a hazardous or unsafe practice which could result in minor injury to personnel, or product or property damage. Note:Identifiesuseful/additionalinformation. Everyefforthasbeenmadetoensuretheaccuracyofthisdocument,however,HoneywellAnalyticscan assume no responsibility for any errors or omissions in this document or their consequences. HoneywellAnalyticswouldgreatlyappreciatebeinginformedofanyerrorsoromissionsthatmaybefound in the content of this document. Forinformationnotcoveredinthisdocument,orifthereisarequirementtosendcomments/corrections aboutthisdocument,pleasecontactHoneywellAnalyticsusingthecontactdetailsgivenonthebackpage. Honeywell Analytics reserve the right to change or revise the information supplied in this document without notice and without obligation to notify any person or organization of such revision or change. If information is required that does not appear in this document, contact the local distributor/agent or Honeywell Analytics.
10
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
2. Introduction 2.1 Searchpoint Optima Plus Searchpoint Optima Plus is an infrared hydrocarbon gas detector suitable for use in hazardous areas. It has worldwidecertificationapprovalsincludingIECEx,ATEX,ULandCSA. It uses the principle of infrared absorption to detect hydrocarbon gases and vapours in various concentration ranges. Standard weather protection
Searchpoint Optima Plus has a robust stainless steel enclosure with an ingress protection level of IP66 and IP67. Dependingonthecertificationoption,it has an M25 or ¾ NPT mounting thread. Searchpoint Optima Plus has a 4-20 mA signal output that corresponds to 0-100 %FSD. Output values below 4 mA indicate fault, warning and inhibit. Certification label Searchpoint Optima Plus is supplied calibratedandlinearisedforaspecific target gas. A wide selection of gases isavailablein0–100%LELrange,as well as some ppm range options. The range0–100%v/vmethaneisavailable exclusively for use in sampling systems.
Gas measuring path
Mounting thread (M25 or ¾ NPT) Inlet / outlet for remote gassing cell
Optional remote gassing cell (use for gas testing or % v/v monitoring)
SearchpointOptimaPluscancommunicatewiththeSHC1HandheldInterrogator,whichcanbeusedto accesscomprehensivediagnosticinformation,andtocarryoutcalibrationandconfiguration.Asanoption, HART®communicationsareavailabletoperformthesamefunctionseitherusingaHART® handheld device or from a central control room. Note:SearchpointOptimaPluscanbeinstalled,commissionedandfunctionallytestedusingonlythe 4-20mAoutput.However,configuration,calibrationandfaultdiagnosisrequireeithertheSHC1Handheld Interrogator,HART® communications or the XNX Universal Transmitter.
11
Searchpoint Optima Plus with optional HART® output Operating Instructions 2108M0550
MAN0905_Issue 7_07/17
2. Introduction 2.2 Searchpoint Optima Plus Options Searchpoint Optima Plus is available in an ethylene version which is optimised for the detection of certain solvents. Searchpoint Optima X is a variant of Searchpoint Optima Plus exclusively for use in sampling systems. A fast speed of response is made possible by minimising the volume of the sample cell. Please contact HoneywellAnalyticsforfurtherdetailsofthisvariant. Searchpoint Optima Z is a variant of Searchpoint Optima Plus optimised for the detection of the solvents ethanolandethylacetate.Itisexclusivelyforuseinsamplingsystems.PleasecontactHoneywellAnalytics for further details of this variant. AllversionsofSearchpointOptimaPluscanbesuppliedwithHART® over 4-20 mA communications.
12
Searchpoint Opt...