DEPARTMENT OF ESTATE MANAGEMENTFACULTY OF ARCHITECTURE, PLANNING AND SURVEYINGUNIVERSITI TEKNOLOGI MARA PERAKGROUP ASSIGNMENT FOLDERCourse code: REM 257Course name: BUILDING MAINTENANCEName of Group Members Matric No MUHAMMAD NAJMIE BIN MOHD NAZIR 2018269418 SARAH NOOR JAIRIN BINTI JAIRI 2018653252 ...


Description

DEPARTMENT OF ESTATE MANAGEMENT FACULTY OF ARCHITECTURE, PLANNING AND SURVEYING UNIVERSITI TEKNOLOGI MARA PERAK GROUP ASSIGNMENT FOLDER Course code: REM 257 Course name: BUILDING MAINTENANCE Name of Group Members

Matric No

MUHAMMAD NAJMIE BIN MOHD NAZIR

2018269418

SARAH NOOR JAIRIN BINTI JAIRI

2018653252

NAS SYAHIERA BINTI MHD RAMLI

2018492028

NUR SHAMIMIE BINTI MOHD ZAID

2018412226

Name of Group Leader: MUHAMMAD NAJMIE BIN MOHD NAZIR Matric No: 2018269418 Assignment Title: BUILDING DEFECT REPORT Due date of Assignment: 8TH JULY 2020 Submission Date : 8TH JULY 2020 Submitted To : Dr. SUWAIBATUL ISLAMIAH BINTI ABDULLAH SANI DECLARATION: We declare that no part of this assignment has been copied from others person work except where due to acknowledgement is made in the text and no part of this assignment has been written for me by any other person except where such collaboration has been authorized by the lecturer concerned. Group’s Leader Signature Date: 7th JULY 2020

najmie A lecturer/tutor has and may exercise a right not to mark this assignment if the above declaration has not been signed. If the above declaration is found to be false, no mark will be awarded for this assignment.

TABLE OF CONTENT NO

CONTENT

PAGE

1.0

ACKNOWLEDGEMENT

3

2.0

INTRODUCTION OF CASE STUDY

4

3.0

INSPECTION PROCESS OF BUILDING DEFECTS ON

5

PROPERTY I 4.0

INSPECTION PROCESS OF BUILDING DEFECTS ON

13

PROPERTY II 5.0

INSPECTION PROCESS OF BUILDING DEFECTS ON PROPERTY III

20

6.0

INSPECTION PROCESS OF BUILDING DEFECTS ON PROPERTY IV

27

7.0

CONCLUSION

37

8.0

REFERENCES

38

9.0

APPENDICES

40

2

1.0 ACKNOWLEDGEMENT First and foremost, praise be to Allah for giving us the chance, perseverance, and strength to finish this assessment on time. With His blessing, He had ease our working process from beginning till the end of this project. This report, however, could not be finished without everybody’s dedication and full effort despite the challenges we have to go through upon finishing this report. Our sincerely gratitude goes to our parents and family who always and inspire us to work hard and focus in everything we do, especially in our studies. Thank you for always praying for our health and wanting us to do our best in our fields. Without their love and care toward us, we might not be able to continue this assignment to the end. Our next gratitude is surely to Dr. Suwaibatul Islamiah bt Abdullah Sani, for guiding us for subject REM 257 Building Maintenance. We are so thankful to have her as our lecturer as patiently and diligently along with helping us finishing this report. Thank you for always trying your best to make the class interesting with whatever ways possible, it has touched our every hearts to see improvements between lecturer and students inside the lecture room. She always ensures that we understand every each of the chapter and guides us patiently throughout ODL due to Covid-19. Her explanation in class gives us good understanding in this subject that encourages us to do the best for this assignment. Not least of all thank you to all the group members, consisting of 4 hardworking members, Muhd Najmie, Sarah Jairi, Nur Shamimie, and Nas Syahiera for the cooperation and full dedication and commitment in completing this task. We went through ups and downs together in hopes that our hard work will pay off in the end. This report could not have been completed without everybody’s effort and their creative ideas throughout this whole process. The guidance and support received from all the members who contributed and who are contributing to this project, was vital for the success of the project.

3

2.0 INTRODUCTION OF CASE STUDY Building maintenance is one of the most important things that the management of the property needs to take care of. To maintain the performance of the building, the property management should carry out an inspection and check all defects and damages in the building to repair or fix the damages to make sure the building in a good condition. Building defects is the building regulation prescribe that material used In the building shall be suitable nature and have a good quality. For your information, every building will face a lot of problems in building defects such as crack, painting defect, door knob broke and others. The defects that occur will ensure that the person who live in the building will take action to overcome that defects and the property will be properly maintained and all of the parts in the building can function as efficiently and effectively. This case study carried out at by every group member’s houses. Everyone in our group carried out the building inspection at their own house and fill in the inspection checklist when inspect all the items in our house. From the inspection, we figure out that a lot of building defects that occur in our house.

4

3.0 INSPECTION PROCESS OF BUILDING DEFECS ON PROPERTY I Type of Property Address Area of subject Property Year Built

Defect

Double Storey Semi Detached House No. 176, Persiaran Venice Intan 5/6, Desa Manjung Raya, 32200, Lumut Perak 35’ x 75’ (2625 sqft) 2009

Defect Sheet Number

Types of Defect

1/6

Ceiling leak stains

Element/ Interior Ceiling Component Descriptions of Defect Dull stains can be seen from the plastered ceiling. Possible Cause of Defect Water leak in or on the ceiling can also result from plumbing leakage or leakage of roofs or other sources of indoor water or high levels of moisture, although leakage from above is the most common cause of water damage to ceilings. The leakage soaks into the ceiling and then evaporates, leaving a layer of stain on the surface. Remedies 1) Firstly, find the source of the leak. 2) If the possibility of source is from the roof, locate and fix cracking shingles, damaged flashing (weatherproofing material installed on the roof) or defective seals around roof vents, both of which may give way to leaks. 3) Later, apply an oil-based coat of stain primer. 4) Repaint the ceiling with a layer of ceiling paint, or using Stormdy Masonry Treatment

5

Cream. 5) Lastly, make sure adequate ventilation is available, so no more moisture will not trap inside the building for further prevention.

6

Defect

Defect Sheet Number

Types of Defect Element/ Component

2/6

Penetrating damp patches on wall Internal Wall

Descriptions of Defect Patches of damp stain are seen on the wall. The wall and its paint are damaged by the dampness. The colour will rust and stain the wall. Possible Cause of Defect The fault is due to the exposure of the wall to damp conditions. This can happen because of leakage to facilities such as pipes, tanks and fittings, or because of penetrating dampness as moisture from outside reaches the internal wall. The leakage soaks into the wall and then evaporates, leaving a layer of stain on the surface. Remedies 1) Carry out visual inspection by using electronic moisture meter readings to check the dampness of the wall. 2) If the issue occurs from service leakage, seek professional help to locate the cause of the problem and remedy it as soon as possible, such as repairing or removing the pipe to avoid the leakage. 3) However, although the area appears moist, is actually dry when checked with a moisture meter then the problem might be from room humidifiers, or humidity from weather. Then, ventilate the house such as seal the gaps around window and door frames. 4) Repaint the wall with wall paint.

7

Defect

Defect Sheet Number

Types of Defect Element/ Component Uneven

3/6

Painting Defect Internal Wall

Descriptions of Defect white plaster is shown

next

to

distribution board. Possible Cause of Defect A layer of paint wall is not applied on top of the plastering after wiring process installed. Remedial Ensure that the fresh colour is consistent with the undercoat. Applying the fresh pain correctly. The finishing coat should be applied from the top to the bottom and done in one operation to clear the joint marks.

8

Defect

Defect Sheet Number

4/6

Types of Defect

Loose Door Knob

Element/ Door Component Descriptions of Defect Unable to close and lock the door because the door knob is not function well due to Loose Door Knob.

Possible Cause of Defect It occurs when the door is unintentionally closed from the inside and the force is used to open the door so that the inside component of the door knob is broken and loose. Remedial Replace Door Knob By using screwdriver or Allen key, loosen the screw and remove the knob that uncovers the shaft. provide some space for the knob to rotate correctly by holding it back and then tighten the screw. In the case of a non-threaded shaft, the knob can be conveniently set back on the shaft and up to the door face until the screw is tightened.

9

Defect

Defect Sheet Number

Types of Defect

5/6

Wires

Sticking

Out

of

Outlets. Element/ Component

Electrical hazard

Descriptions of Defect Screw terminal connections at wall switches and outlets are loose. Besides, eventually leads to the chances of a fire, in case the socket is combustible. Possible Cause of Defect Wires fall out of the socket due to insufficient wires or faulty wiring. Because these fixtures are used more frequently in electrical components. Remedial Firstly, switching off the power to the supposed wall switch. Prepare tools such as flat-head screwdriver, Philips screwdriver, replacement outlet (if needed), voltage tester, Remove the cover plate and use a flashlight to carefully inspect the inside screw terminals where the wires are attached. In case any that's loose, cautiously tighten the screw terminals down on the wires. Bending the outside wires of the plug will help the wire remain in the outlet Next, make sure the new socket is securely sealed, so that the tool can't wiggle when insert or remove plugs.

10

Defect

Defect Sheet Number

Types of Defect

6/6

Dis-function of the window

Element/ Casement window Component Descriptions of Defect The window cannot be completely closed and caught up at a certain point. Difficulty in opening and shutting the glass panel. Possible Cause of Defect Possibility of dis-alignment of frames and glass panels or improper prevention resulting in debris entering the friction track will cause the window to stuck. Besides, improper installation of friction and pivot brackets. Remedial Check the alignment of the outer frames and the inner panels and clear the track of all debris. Next, remains to check the conditions of friction stays. If it broken or rusting, try to replace a new friction stays for casement window. Lastly, apply lubricant to every moving area of the window. Lubrication is recommended for the prevention of harm at least once a year.

11

Figure 3.0 shows that the building inspection checklist of No. 176, Persiaran Venice Intan 5/6, Desa Manjung Raya, 32200, Lumut Perak.

12

4.0 INSPECTION PROCESS OF BUILDING DEFECTS ON PROPERTY II Type of property

Single storey house

Address

Lot 1147 Batu 32 ½ Kampung Sungai Siput 78100 Lubuk China, Melaka

Area of subject property

41’ x 46’

Year built

2017

Defect

Defect sheet number

1/6

Type of defect

Wall defect

Element/ component

Internal wall finishes

Description of defect There are cracks that occur on the surfaces of the internal wall finishes of the house. Possible cause of defect Contraction and expansion of the materials such as paint or plaster. This is usually a problem if the wall is within a room that is periodically air-conditioned or it faces the afternoon sun quite a bit. The movement of contraction and expansion can cause cracks to appear. Remedial First step is to create a deeper hairline crack by using a scrapper before starting the repair work. Fill it with filling solution/joint compound. Make sure the filler covers the entire crack. Then apply paint. If the painter applies two coats, always make sure the first coat has properly dried before applying the second coat.

13

Defect

Defect sheet number

2/6

Type of defect

Loose door knob

Element/ component

Door

Description of defect When then door knob broke, the door is unable to close and lock the door as the part inside the knob is missing. Possible cause of defect This problem happens when the door is accidently locked from inside and the house occupant’s force is being use in order to open the door and door knob broke. Remedial This defect can be solving by installing a new door knob. Use a screwdriver to remove the existing knob from the interior side of the door. This will release the knob and allow you to pull the knobs off of both sides of the door. Remove the screws from the latch plate located on the inside edge of the door. Insert the new door knob latch on the inside edge of the door. Put this new knob and spindle through the latch you just installed. Align the parts and secure in place Lastly, test the new doorknob to make sure everything is installed correctly.

14

Defect

Defect sheet number

3/6

Type of defect

Heating, Ventilation and Air-conditioning system (HVAC)

Element/ component

Air-conditioning

Description of defect This happen when the air-conditioning switch on and after a few minutes of air-conditioning operating the water will drop down from the air-conditioning. Possible cause of defect Lack of regular maintenance. Remedial Shutdown and unplug the air conditioning unit. This is to ensure the safety for the house occupant. Unscrew the access panel to locate the condensate drain pan. The condensate drain is at a saturation point under the evaporating coils. Check whether water is overflowing from the pan. If there is overflow occur, the odds are that the drain channel is clogged. Soak the water and wash the pan with a piece of dry cloth.

15

Defect

Defect sheet number

4/6

Type of defect

Painting defect

Element/ component

Internal wall finishes

Description of defect The surface of the internal wall of house do not smooth as it should be and the painting do not cover up the wall surfaces and have sagging Possible cause of defect This defect causes by poor applying method and low quality of paint. Remedial The painter need to scrap the defects surface and paint back the wall with sealant powder. Before paint back, the painter must make sure the surface is clean. If the paint is still wet, brush or roll out the excessive paint so that it is in harmony with the remaining paint coat.

16

Defect

Defect sheet number

5/6

Type of defect

Floor

Element/ component Floor cement crack Description of defect There are cracks occur on the cement floor Possible cause of defect Tensile strength applied to the cement floor Remedial Use a cold chisel and a hammer to get rid of any large pieces in the crack. Clean up and get rid of dust and debris. Use the concrete filler, cut the nozzle off the bottle and slowly fill the cracks. If using mixed concrete patch, mix according to the manufacturer's direction and then trowel the patch into the crack. After patching the concrete, it will be better when we seal it.

17

Defect

Defect sheet number

6/6

Type of defect

Ceiling lighting

Element/ component

LED light

Description of defect The LED light do not light up when switch on the switch of the lamp. Possible cause of defect The bulb may be loose or the circuit breaker has tripped or the fuse of the lamp burns out Remedial This bulb need to be replace. When the replacement process occurs, the switch need to turn off. Remove the old bulb from the light. Place the replacement LED bulb in the fixture and screw it into place. Turn the bulb slowly so that it goes down evenly onto the threads of the fixture's screw. Restore power to the fixture by plugging it back in. Turn on the light and be sure that it is functional.

18

Figure 4.0 shows the building inspection checklist of Lot 1147 Batu 32 ½ Kampung Sungai Siput 78100, Lubuk China, Melaka

19

5.0 BUILDING INSPECTION OF PROPERTY III Types of Property

Single Storey House 34-A Kampung Banggol Binjai, Tepoh,

Address

21060 Kuala Nerus Terengganu.

Area of Property

40’ x 80’

Defect Sheet

Defect

1/6

Number Types of Defect

Crack Wall cement

Element/Component

crack

Description of Defect This defect can make the surface of the wall uneven thus making the sound from the other room can be heard. It also reduces the look of the wall surface.

Possible Cause of Defect Tiny hairline cracks in the plaster walls can be mostly cosmetic and may be induced by a gradual contraction and expansion of the house's wood frame through seasonal shifts. Other cracks in internal walls may be indicators of more serious underlying issues, such as subsidence,

poor

initial

design

or

structural and fundamental defects. Remedial Demolition and restructuring: In certain severe

situations,

demolition

and

repairing the wall might be the only way to fix the triggers of the cracking of the wall if there is a significant structural defect. 20

Defect Sheet

Defect

2/6

Number Types of Defect

Hole crack

Element/Component

Ceiling

Description of Defect Rodents and other chewing pest: Due to this subject property is located in a rural area, the residents are no strangers to the pest. So, when flowing waters interrupt their habitats, rats, mice, and other creatures, head to higher, dryer soil, which may take the form of the attic. Bite marks in the corners and other telling signs that a living creature is calling the attic home. Possible Cause of Defect Usually, there are some pests such as rodents that occupy the attic and make the hole as their exit and stay in the attic. They will leave a bite mark on the ceiling asbestos.

Remedial Remove the broken ceiling tiles from the frame. Replace a new ceiling tiles to its place.

21

Defect Sheet

Defect

Number

3/6

Types of Defect

Uneven paint

Element/Component

Wall

Description of Defect This uneven paint color on the wall is due to the replacement of the old TNB meter becau...